Wind turbine blade thermography
Detection of missing adhesive, delaminations and internal defects without touching the blade
Missing adhesive shows up in the temperature
A wind turbine blade is a hollow fibreglass structure bonded with adhesive: the two shells are glued to each other at the leading and trailing edges, and the internal shear webs are glued to the shells. When adhesive is missing from one of those joints, from the factory or after a repair, the blade keeps working, but that area heats up and cools down at a different rate from the rest.
With a high-resolution radiometric thermal camera, flying at the time of day when the blade is changing temperature, that difference shows up as a blotch in the image. We locate it, measure it and place it in metres from the root so the maintenance team knows exactly where to open.
It is the most demanding thermographic inspection we do and the one that has defined our method: the same camera and the same team carry out thermographic inspection of power lines, substations, solar plants and industrial roofs in any country.
A thermographic inspection campaign, step by step
Planning
We analyse the wind farm, the turbine model and the forecast weather to choose the flight hours with the greatest thermal contrast, usually early in the morning or late in the afternoon.
Stop and positioning
The turbine is stopped and locked with the blades in the inspection position. A two-person team, pilot and technician, inspects between 6 and 10 machines a day.
Thermal and visual flight
We fly each blade along the suction side, pressure side, leading edge and trailing edge. Every thermal image comes with its 48 MP visual image and the laser-measured distance to locate the defect.
Analysis and report
We review the radiometric images, classify each anomaly and deliver a report per turbine and a summary table of the wind farm with priorities.
The inspection camera
Any thermal camera will not do. To see a missing-adhesive area of a few centimetres from 10 metres away you need resolution and sensitivity.
thermal resolution, 12 µm microbolometer
thermal sensitivity (NETD): distinguishes 0.05 °C
radiometric measurement range
wide-angle camera and 34× hybrid zoom for the visual image
laser rangefinder to position every defect
works in wind, dust and humidity
What the camera sees
Three captures from our campaigns: missing adhesive at the shell joint, a debonded area on the suction side and the whole blade with a hot leading edge.
What you get at the end
A thermographic report per turbine with a sheet per blade: radiometric thermal and visual image of each anomaly, position in metres from the root, blade face, approximate dimensions, temperature rise relative to the sound area and severity classification. A summary table of the wind farm with all anomalies ranked by repair priority. And the original radiometric images, so your technical team can re-measure them with its own software.
If you prefer, we deliver the results in the format of your asset management platform, and on periodic campaigns we compare each blade with the previous inspection to see which anomalies have grown.
Top-level thermographers
We are top-level certified thermographers and ISO 14001 auditors. We measure temperature with a radiometric camera, we do not just take thermal images: every anomaly is quantified, located in metres from the root and interpreted knowing what material lies beneath and which defect may explain it. And we deliver it with an auditor’s rigour: classification criteria defined in advance, traceability of every measurement and a report your technical team can review and repeat.
Beyond blades, with the same camera we inspect power lines, substations, solar plants and industrial roofs. On lines we combine thermography with high-resolution visual inspection and automatic identification of insulator defects using artificial intelligence.
Frequently asked questions
Does the turbine have to be stopped for the thermographic inspection?
Yes. To obtain sharp images and be able to locate each defect, the machine is stopped and locked during the flight, between 20 and 40 minutes per turbine depending on blade size. The rest of the wind farm keeps producing.
At what time of year can it be done?
All year round, as long as there is thermal contrast. The best results are obtained on sunny days and in the hours when the blade is heating up or cooling down. In winter or under overcast skies we adjust the flight hours.
Which defects are detected besides missing adhesive?
Delaminations, internal cracks with water ingress, leading-edge detachment, lightning damage to the protection system and repaired areas with excess or insufficient material.
How many turbines do you inspect per day?
Between 6 and 10 per team, depending on the distance between machines and the stops. For large wind farms we deploy several teams in parallel.
Do you deliver the original radiometric images?
Yes, always. Along with the PDF report you receive the radiometric files of each anomaly and of each whole blade, so your team can re-measure temperatures, change the palette or compare with previous campaigns.
Where do you work?
On wind farms in any country. A two-person team travels with the drone, the camera and the spare parts in a single vehicle.