Live-line insulator washing by drone
Up to 500 kV, without de-energising the line, with demineralised water. In Spain, Morocco, Algeria and Cyprus
Why insulators are washed
In coastal, industrial or desert areas, salt, dust and pollution settle on the insulators of high-voltage lines. With humidity, that layer becomes conductive and causes leakage, flashovers and, in the worst case, line trips. Utilities wash insulators periodically to maintain the insulation level, and they do it live so as not to interrupt supply.
Live washing requires demineralised water, with conductivity below 0.05 µS/cm, and a controlled jet that does not create a conductive path between the conductor and the tower. It is specialist work, and we have been doing it for 35 years.
From helicopter to drone
We come from HeliTecnics, the company that washed over one million insulators by helicopter in more than 20 countries. In 2022 we brought that trade to the drone with our own system, the Helion X1: a 2,000 psi pump, a 100-litre tank and a 2.5 m insulated lance carried on a heavy-lift drone.
The drone does the same job with less noise, lower cost and without de-energising the line. Today we wash for utilities and contractors in Spain, Morocco, Algeria and Cyprus: 8,500 insulators by drone in 2026 and 45,000 contracted for 2027.
One team, 250 insulators a day
A pilot and a technical operator reach the tower by 4×4 with the drone, a generator, a 1,000 l auxiliary tank of demineralised water and the conductivity meters to check it. The drone takes off with 100 l of water, washes string by string with a jet reaching 5 to 7 m and reloads in under 2 minutes. The batteries recharge in 9 minutes.
At the end of the day we deliver the washing certificate per tower and string, with water consumption, the conductivity measured for each load and the incidents observed (broken insulators, rusted fittings, nests). We wash glass, porcelain and composite insulators on lines up to 500 kV. If you need it, we combine the campaign with thermographic and visual inspection of the line.
| Method | Market cost per insulator | Line |
|---|---|---|
| Helicopter | €85 – 120 | Live |
| Water truck | €60 – 80 | Live, road access only |
| Helion drone | On request | Live, any access |
Frequently asked questions
What do we need to request a quote?
The line type and the approximate number of insulators, the area and access conditions, the type of contamination, the availability of nearby water and the planned schedule. With that we prepare a price per string.
Does the line have to be de-energised?
No. We wash live up to 500 kV with demineralised water and the utility’s safety distance procedure. We can also work with the line de-energised if the client prefers.
Where does the demineralised water come from?
The client supplies it or we produce it with reverse osmosis and deionisation units. In all cases we measure conductivity before every load.
Do you wash in substations?
Yes, with the C1 system in its insulated E1 version, designed to work in confined spaces with a dielectric hose. In substations the operation requires an experienced pilot and a prior study.
How many insulators have you washed by drone?
Around 8,500 in 2026 in Spain, Morocco and Cyprus, and we have 45,000 contracted for 2027. Before the drone, our team washed over one million insulators by helicopter in more than 20 countries.